Capacity |
1kVA to 20kVA Air Cooled |
Input Voltage Range |
110-270V, 140-270V, 170-270V |
System |
3 Wire (P,N+E) |
Input Frequency |
47 to 53 Hz |
Output Voltage Adjustable |
220 to 240V AC |
Speed of Correction |
Up to 60V/Sec |
Output Voltage Regulation |
± 1% (No Load) |
Ambient Temperature |
0 to 55 C |
Overload Capacity |
1.2 |
Waveform Distortion |
True Reproduction of Input |
Insulation |
Class F |
Mode of System |
Fully Automatic/Manual |
Protection |
Low Voltage Protection, High Voltage Protection and Overload Protection, Short-circuit Protection and power ON/OFF of SCVS through MCB at Input |
Optional Features |
Bypass switch at Input to bypass the equipment in case of emergency |